Metric thread sizes
All values in mm unless stated.
| Size | Outside Ø d | Pitch P | Tap drill Ø | Clearance hole Ø |
|---|---|---|---|---|
| M12×1.5 | 12.00 | 1.5 | 10.5 | 12.5 |
| M16×1.5 | 16.00 | 1.5 | 14.5 | 16.5 |
| M20×1.5 | 20.00 | 1.5 | 18.5 | 20.5 |
| M25×1.5 | 25.00 | 1.5 | 23.5 | 25.5 |
| M32×1.5 | 32.00 | 1.5 | 30.5 | 32.5 |
| M40×1.5 | 40.00 | 1.5 | 38.5 | 40.5 |
| M50×1.5 | 50.00 | 1.5 | 48.5 | 50.5 |
| M63×1.5 | 63.00 | 1.5 | 61.5 | 63.5 |
Tap drill = d − P, for a tapped wall. Clearance hole for a gland held by a lock nut, as tabulated in EN 50262 (tolerance +0.2 / −0.4 mm). AirGrip glands and accessories also come in M80. Choosing a gland: how to select a cable gland.
Metric glands and accessories
Glands, lock nuts, stop plugs and adapters in metric threads.